ResearchConference paper Accepted
Rooppur NPP Water Security & Thermal Risk
Water security and thermal risk of Bangladesh's first nuclear plant on the Padma.
Overview
The Rooppur Nuclear Power Plant will withdraw cooling water from the Padma River, whose discharge varies by more than two orders of magnitude between seasons. This study assesses the plant's water-security and thermal risks using 32 years (1990-2021) of daily discharge at the Hardinge Bridge gauge and 500 discharge measurements (2017-2019).
A Water Stress Index (WSI) was computed for demands of 6, 9.77, and 18 m3/s. For 6-9.77 m3/s the WSI never exceeded 3.7%, below the 5% low-risk limit; for 18 m3/s it exceeded 5% on 42 recorded days, with a maximum of 6.9%. The record low flow of 261 m3/s in March 1993 is the governing condition.
The fully mixed temperature rise from cooling-tower blowdown was at most 0.025 °C. Near the bank, the depth-averaged excess temperature fell below 1 °C within about 370 m at the 5th-percentile flow and 2.5 km at the record low. The results support continuous flow and temperature monitoring, a WSI-based operating rule, and an outfall designed for rapid dilution.
Highlights
- 01
32-year discharge record
Daily Padma flow at the Hardinge Bridge gauge, 1990-2021.
- 02
Water Stress Index
Demand scenarios of 6, 9.77, and 18 m3/s against the 5% low-risk limit.
- 03
Thermal plume
Fully mixed heat balance and near-bank plume model.
More engineering & research
Research· 2026
Seismic Evaluation of a 58-Year-Old RC Academic Building
BSPP second-level screening of a legacy three-storey RC building at CUET.

Research· 2025
Vertical Extension of a Civil Engineering Building
B.Sc. thesis: a 7-storey steel extension over a 1968 RCC building, without touching it.
Research
G+4 Residential Building, PinkCity, Raozan
Complete structural design and analysis of a residential building to BNBC 2020.